60 Advanced Operations Smart Cabinet Distribution Unit
Installation and Operations Manual
Setting the Humidity sensor threshold limits:
The Set Trap THS Humidlow and Set Trap THS Humidhigh commands are used to set the lower and
upper threshold limits for the Humidity sensor.
To set the Humidity threshold limits:
At the Smart CDU: prompt, type set trap ths, humidlow or humidhigh, followed by the sensor name
and a value from 0 to 100 in percent relative humidity. Press Enter.
Example
The following command sets the first humidity sensor low threshold limit to 5:
Smart CDU: set trap ths humidlow .a1 5<Enter>
Displaying trap configuration information:
The Show Traps command displays information about all traps.
To display trap information:
At the Smart CDU: prompt, type show traps and press Enter.
Example
The following command requests trap configuration information:
Smart CDU: show traps <Enter>
Tower trap configuration:
Tower Tower Status
ID Name Trap
.A Florida_HQ_1 ON
.B Florida_HQ_2 ON
More (Y/es N/o): y
Input feed trap configuration:
Input Input Status Load High
Feed ID Feed Name Trap Trap Thresh
.AA HQ_1_Infeed_A ON ON 255 A
.BA HQ_2_Infeed_A ON ON 255 A
More (Y/es N/o): y
Environmental Monitor .A trap configuration:
Name: Florida_HQ_1
Status Trap: ON
Temperature/Humidity Sensor .A1 Temperature/Humidity Sensor .A2
Name: Temp_Humid_Sensor_A1 Name: T/H2_Florida_HQ_1
Status Trap: ON Status Trap: ON
Temp Trap: ON Temp Trap: ON
Low: 0 Deg.C Low: 0 Deg.C
High: 127 Deg.C High: 95 Deg.C
Humid Trap: ON Humid Trap: ON
Low: 5 % RH Low: 0 % RH
High: 100 % RH High: 100 % RH