Server Technology PT40 Installationshandbuch Seite 42

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 90
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 41
42 Operations Smart Cabinet Distribution Unit
Installation and Operations Manual
Setting the filename to be uploaded:
The Set FTP Filename command sets the filename of the firmware file to be uploaded.
To set the FTP filename:
At the Smart CDU: prompt, type set ftp filename, followed by the firmware filename and press Enter.
Example
The following command sets the FTP filename to snb_s50a.bin:
Smart CDU: set ftp filename snb_s50a.bin<Enter>
Setting the directory for the file to be uploaded:
The Set FTP Directory or Set FTP Filepath commands set the directory for the firmware file to be
uploaded.
To set the FTP directory:
At the Sentry: prompt, type set ftp directory, followed by the directory and press Enter.
Or, type set ftp filepath, followed by the directory and press Enter
Example
The following command sets the FTP directory to ftp://Sentry:
Sentry: set ftp directory ftp://sentry<Enter>
Enabling or disabling automatic updates:
The Set FTP Autoupdate command is used to enable or disable automatic firmware update support.
To enable or disable automatic updates:
At the Smart CDU: prompt, type set ftp autoupdate, followed by enabled or disabled and press Enter.
Setting the automatic update scheduled day:
The Set FTP Autoupdate Day command is used to set the day when automatic updates occur.
To set the automatic update day:
At the Smart CDU: prompt, type set ftp autoupdate day, followed by a day of the week or everyday and press
Enter.
Example
The following command sets the automatic update day to Sunday:
Smart CDU: set ftp autoupdate day sunday<Enter>
Setting the automatic update scheduled hour:
The Set FTP Autoupdate Hour command is used to hour of the day when automatic updates occur.
To set the automatic update hour:
At the Smart CDU: prompt, type set ftp autoupdate hour, followed by an hour of the day and press Enter.
Examples
The following command sets the automatic update hour to 12 AM:
Smart CDU: set ftp autoupdate hour 12am<Enter>
The following command sets the automatic update hour to 3 PM:
Smart CDU: set ftp autoupdate hour 3pm<Enter>