32 • Operations Smart Cabinet Distribution Unit
Installation and Operations Manual
Input Feed Administration
Creating a descriptive infeed name:
The Set Infeed Name command assigns a descriptive name to an infeed. This descriptive name is
displayed when the Show Traps command is issued. See
Displaying trap configuration information on
page
60 for more information on the Show Traps command.
To create a infeed name:
At the Smart CDU: prompt, type set infeed name followed by the absolute infeed name, then a
descriptive name of up to 24 alphanumeric and other typeable characters - (ASCII 33 to 126 decimal)
are allowed; spaces are not allowed. Press Enter.
Example
The following command adds the descriptive name HQ_1_Infeed_A to the infeed on the Smart CDU:
Smart CDU: set infeed name .aa HQ_1_Infeed_A<Enter>
Setting the infeed operational voltage
The Set Infeed Voltage command is use to edit the input operational voltage.
To set the infeed operational voltage:
At the Smart CDU: prompt, type set infeed voltage, followed by the absolute infeed name, and a value
from 0 to 480. Press Enter.
Example
The following commands sets the operational voltage for input .AA to 100V:
Smart CDU: set infeed voltage .aa 100<Enter>
Setting the infeed maximum load capacity
The Set Infeed LoadMax command is use to edit the input maximum load capacity.
To set the infeed maximum load capacity:
At the Smart CDU: prompt, type set infeed loadmax, followed by the absolute infeed name, and a
value from 1 to 255 (in amperes). Press Enter.
Example
The following commands sets the maximum load capacity for input .AA to 15 amperes:
Smart CDU: set infeed loadmax .aa 15<Enter>
Displaying infeed information:
The Show Infeeds command displays information about all infeeds. This information includes the
absolute and descriptive infeed names, operational voltages and maximum load capacities.
To display tower information:
At the Smart CDU: prompt, type show infeeds and press Enter.
Example
Smart CDU: show infeeds<Enter>
Input Input Input Input
Feed ID Feed Name Feed Voltage Feed Capacity (Amps)
.AA HQ_1_Infeed_A 100 15
.AB HQ_1_Infeed_B 120 20
.BA HQ_2_Infeed_A 120 30
.BB HQ_2_Infeed_B 120 30