54 Advanced Operations Smart Cabinet Distribution Unit
Installation and Operations Manual
Setting the trap timer:
The Set Traptime command sets the timer period between repeated error-condition traps. The valid
range for the timer period is 1 to 65535 (in seconds).
The default value for the timer period is 60 seconds.
To set the trap timer:
At the Smart CDU: prompt, type set traptime, followed by the timer period and press Enter.
Example
The following sets the timer period to 180 seconds:
Smart CDU: set traptime 180<Enter>
Setting the Get/Set community strings:
Sentry supports two SNMP community strings that provide varying levels of access to objects defined
in the Sentry3 MIB.
Community strings may be 1 to 24 characters.
Setcomm:
The Setcomm string provides read-write access to sentry3 MIB objects.
The default Setcomm string is “private”
To set the Setcomm community string:
At the Smart CDU: prompt, type set snmp setcomm, followed by the string and press Enter.
Getcomm:
The Getcomm string provides read-only access to sentry3 MIB objects.
The default Getcomm string is “public”.
To set the Getcomm community string:
At the Smart CDU: prompt, type set snmp getcomm, followed by the string and press Enter.
Setting SNMP IP Restrictions:
The Set SNMP IP Restrictions command supports SNMP Manager GET and SET requests to only be
allowed from the IP addresses of the defined traps destinations.
To set SNMP IP Restrictions:
At the Smart CDU: prompt, type set snmp iprestrict trapdests and press Enter.
To remove SNMP IP Restrictions:
At the Smart CDU: prompt, type set snmp iprestrict none and press Enter.
Setting the SNMP SysName:
The Set SNMP SysName command is used to set the SNMP MIB-II SysName object.
To set the SysName object:
At the Smart CDU: prompt, type set snmp sysname, followed by the object name and press Enter.
Setting the SNMP SysLocation:
The Set SNMP SysName command is used to set the SNMP MIB-II SysLocation object.
To set the SysLocation object:
At the Smart CDU: prompt, type set snmp syslocation, followed by the object location and press Enter.
Setting the SNMP SysContact:
The Set SNMP SysName command is used to set the SNMP MIB-II SysLocation object.
To set the SysContact object:
At the Smart CDU: prompt, type set snmp syscontact, followed by the object contact and press Enter.