Smart Cabinet Distribution Unit Advanced Operations 57
Installation and Operations Manual
Temp Trap
The Temp trap is generated whenever the temperature on a temperature/humidity sensor is beyond
preset thresholds. Temp traps include the reported temperature, temp status, Location of the Sentry,
and identifier and name of the affected sensor.
Any error state generates a Temp trap and triggers the trap timer. A new trap is generated at the end of
every timer period until the Temp returns to a non-error status.
Temp traps
Status Error Description
Normal The sensor is working correctly and the temperature is within preset thresholds
NotFound No sensor has been detected
Reading Temp status currently being read
TempLow x Temperature at the sensor below preset low threshold
TempHigh x Temperature at the sensor exceeds preset high threshold
ReadError x Unable to read Temp status
Lost x Sensor initially detected but communication to the sensor has been lost
NoComm x Communication to the sensor has been lost
Humidity Trap
The Humidity trap is generated whenever the humidity on a temperature/humidity sensor is beyond
preset thresholds. Humidity traps include the reported relative humidity, humidity status, Location of
the Sentry, and identifier and name of the affected sensor.
Any error state generates a Humidity trap and triggers the trap timer. A new trap is generated at the end
of every timer period until the Humidity returns to a non-error status.
Humidity traps
Status Error Description
Normal The sensor is working correctly and the relative humidity is within preset thresholds
NotFound No sensor has been detected
Reading Humidity status currently being read
HumidLow x Relative humidity at the sensor below preset low threshold
HumidHigh x Relative humidity at the sensor exceeds preset high threshold
ReadError x Unable to read Humidity status
Lost x Sensor initially detected but communication to the sensor has been lost
NoComm x Communication to the sensor has been lost