Appendix C: Technical Specifications
Domestic Models
Model Voltage Inlet* Outlets Additional Ports
PT40-H404-1-02 100-120V, 50/60Hz IEC 60320 C20 4 NEMA 5-20R 4 Pass-Thru
PT40-H404-2-02 208-240V, 60Hz IEC 60320 C20 4 IEC 60320 C13 4 Pass-Thru
International Models
Model Voltage Inlet* Outlets Additional Ports
PT40-H404-2-02 230V, 50/60Hz IEC 60320 C20 4 IEC 60320 C13 4 Pass-Thru
* Input cordset selected at time of purchase. (Contact your account representative for more information).
Power Ratings
1
All current ratings are in amperes. Tous les indices de courant sont en ampères. Alle Angaben der Stromstärke erfolgen in Ampere.
Physical Specifications
Operating Storage
Temperature 32° to 122° F (0° to 50° C) -40° to 185° F (-40° to 85° C)
Elevation(above MSL) 0 to 10,000 ft (0 to 3000m) 0 to 50,000 ft (0 to 15000m)
Relative Humidity 10 to 90%, non-condensing 10 to 90%, non-condensing
Dimensions (H x W x D) Weight
PT40-H404 1.75 x 17.0 x 7.0 in. (45 x 432 x 178 mm) 8.2 lbs (3.7 kg)
Model
olta
e Current
olta
e Outlet Branch Circuit Phase Total
Modele Tension Courrant Tension Prise
Circuit de la Branche
Total
Modell Spannung Strom Spannung Anschlussstelle Zweigstromkreis Insgesamt
PT40-H404-1-02
100-120V
50/60Hz
16
100-120V
50/60Hz
16 n/a 16
208-240
60Hz
16
208-240
60Hz
12 n/a 16
230V
50/60Hz
16
230V
50/60Hz
10 n/a 16
Eingangsstromstärke Ausgangsstromstärke
PT40-H404-2-02
Input Current Rating
1
Output Current Ratings
L’indice du courant d’entrée L’indice du courant de sortie
Sentry Commander - PT40 Appendices • 67